MODEL: Nx9940 Nx9960 Nx9980 Nx99100 Nx99120 Nx99160 Nx99200
Capacity: 40 kVA/40 kW 60 kVA/60 kW 80 kVA/80 kW 100 kVA/100 kW 120 kVA/120 kW 160 kVA/160 kW 200 kVA/200 kW
INPUT:
Input wiring: Three-phase five-wire (?? + N + PE)
Rated voltage: 380/400/415 Vac
Voltage range: 304-485 Vac (no downgrading), 138-304 Vac (linear downgrading between 40%-100% load)
Rated frequency: 50/60 Hz (auto-sensing)
Frequency range: 40-70 Hz
Power factor: ?0.99
Bypass voltage range: -60%~+20% (settable)
Total harmonic distortion (THDI): ?3%
OUTPUT:
Output wiring: Three-phase five-wire (3$ +N+PE)
Rated voltage: 380/400/415 Vac
Voltage regulation: ±1%
Frequency: Synchronized with utility in mains mode, 50/60 Hz ±0.1% in battery mode.
Waveform: Sinusoidal
Power factor: 1
Total harmonic distortion (THDv): ?1% (linear load); ? 4% (non-linear load)
Crest factor: 3:1
Overload: 105%~110% for 60 min, 110%~125% for 10 min, 125%-150% for 1 min, 150% for 0.2 s
BATTERIES:
DC voltage: ±192 Vdc (±180~±264 Vdc settable) 40 kVA built-in battery: ± 240 Vdc (80 pcs 9 Ah/12 V)
Number of battery: 32 pcs (30-44 pcs settable)
Charging current (max.:12A 24A 36A 48A
Recharge time: Depend on the capacity of battery
SYSTEM:
Operating temperature: 0°?-40?
Storage temperature: -25°C-55°C (without battery)
Relative humidity: 0%-95% (non-condensing)
Altitude: ? 1000 m; above 1000 m, downgrading 1% for each additional 100 m
IP rating: IP 20
Noise level at 1 m: ?65 dB
Dimensions (WDH) (mm): 360 * 850*885 , 360*850*950 , 360 * 850*885*1200 , 440 * 850 * 1200 , 600 * 850 * 1200
Packaged dimensions (WDH) mm): * 1055 450 * 940 , 450 * 940 * 1120 , 450 x 940 x 1370 , 530 * 940 * 1370 , 700 * 950 * 1370
Net weight (kg): 95, 295 (built-in BAT) 130 156 158 198 250 300
Gross weight (kg): 110, 310 (built-in BAT), 145, 172, 180,220 275 325