MODEL: Nx3310 Nx3315 Nx3320 Nx3330 Nx3340 Nx3360 Nx3380 Nx3100 Nx3120
Capacity: 10 kVA /9 kW , 15 kVA /13.5 kW , 20 kVA /18 kW , 30 kVA /27 kW , 40 KVA /36 kW 60 kVA /54 kW , 80 kVA /72 kW , 100 KVA /90 kW , 120 kVA /108 kW
INPUT:
Input wiring: Three-phase five-wire (3Ø + N + PE)
Rated voltage: 380/400/415 Vac
Voltage range: 285-475 V
Rated Frequency: 50 Hz
Frequency range: (50) ± 5 Hz
Power factor: ? 0.95 (with Filter)
Delayed start of rectifier: 10 s (1300 settable)
Bypass voltage range: ± 20% (settable)
OUTPUT:
Output wiring: Three-phase five-wire (3 + N + PE)
Rated voltage: 380/400/415 Vac
Output Voltage regulation: ± 1%
Waveform: Sinusoidal
Power factor: 0.8
Voltage distortion (THDv): ?1% (linear load); ? 5% (non-linear load)
Crest Factor: 3:1
Overload: 105%~110% for 60 min, 105%~110% for 20 secs
Output Frequency regulation: 50 Hz ± 0.1% Hz in battery mode
BATTERIES:
DC Voltage: Lead acid battery: 360 Vdc Lithium iron phosphate battery: 384 Vdc
Number of battery: Lead Acid battery: 12 V x 30 pcs (support 28~32 pcs) Lead Acid battery: 2 V x 180 pcs (support 168-192 pcs) Lithium iron phosphate battery: 3.2 V x 120 pcs (support 112/120 pcs)
Charging current: Charging rate (settable) x battery capacity (settable) x number of battery groups (settable)
SYSTEM:
Efficiency: In Line mode: Max. 95%
Protections: Short-circuit, overload, over temperature, battery low voltage, over voltage, under voltage and fan failure
Communications: RS232/RS485 / dry contacts (standard), SNMP (optional)
EMI: EN62040-2
EMS: IEC61000-4-2 (ESD) IEC61000-4-3 (RS) IEC61000-4-4-(EFT) IEC61000-4-5 (surge)